Surge Protection For AC Power Supplies 2 x VAL-MS 320/40/1+0 GY1

Surge arresters consisting of base element and protective connector with high-capacity varistor, for mounting on NS 35/7.5, 1-channel

Description

Nominal voltage UN : 240/415 V AC

1-phase TN-S, 240/415 V AC, Class II, 40 KA (8/20µs)

P/N : 2 x VAL-MS 320/40/1+0 GY1

- Single-channel, DIN-rail mountable protective devices.

- Disconnect device on each individual plug.

- Optical, mechanical status indication for the individual arresters.

IEC Tested Class II, T2
Max.Continuous Voltage Uc 335 V
Impulse current Iimp (10/350) µs-
Maximum discharge current Imax (8/20) µs40 kA
Nominal discharge current In (8/20) µs20 kA
Voltage protection level Up≤ 1.5 kV
Follow Current interupt rating Ifi-
Remote indication contact-
Test standardIEC61643-11

หรือสอบถามเพิ่มเติม
▶️ LINE ID: @bluestone
▶️ Email: infos@bluestone.co.th
▶️ Telephone: 02-726-1585-88 ,084-160-6298
▶️ Website: https://www.bluestone.co.th/contactus