Description
Nominal voltage UN : 240/415 V AC
3-phase TN-S, 240/415 V AC , Class I/II, 25 KA (10/350µs)
P/N : FLT-SEC-P-T1-3S-350/25-FM
- Spark gap has no line follow current.
- Free of leakage current, suitable for use in the pre-meter area.
- High continuous voltage of 264 V AC for 230/400 V AC networks.
IEC Tested Class | I/II, T1/T2 |
Max.Continuous Voltage Uc | 350 V |
Impulse current Iimp (10/350) µs | 25 kA |
Maximum discharge current Imax (8/20) µs | 50 kA |
Nominal discharge current In (8/20) µs | 25 kA |
Voltage protection level Up | ≤ 1.5 kV |
Follow Current interupt rating Ifi | 50 kA |
Remote indication contact | PDT contact |
Test standard | IEC61643-11 |