F-MS 12 GY1 Type2 surge protection อุปกรณ์ป้องกันฟ้าผ่า

SKU : 2801280

Type 2 surge protection device – F-MS 12 GY1 – 2801280

Surge arrester type 2, consisting of base element and protective plug with N-PE total current spark gap for mounting on NS 35/7.5, housing width: 17.5 mm (1 Div.)

ออกใบกำกับภาษีได้

รับประกันสินค้า

฿1,810.00

รายละเอียดสินค้า

Type 2 surge protection device – F-MS 12 GY1 – 2801280

– IEC test classification: II, T2
– EN type: T2
– Number of positions: 1
– Surge protection fault message: optical

Insulation characteristics
– Overvoltage category: III
– Pollution degree: 2

Mode of protection: N-PE
– Direction of action : N-PE
– Nominal voltage UN: 240/415 V AC (TN – only N-PE), 240/415 V AC (TT – only N-PE)
– Nominal frequency fN: 50 Hz (60 Hz)
– Maximum continuous voltage UC: 260 V AC
– Rated load current IL: 80 A
– Residual current IPE: ≤ 5 µA
– Standby power consumption PC: ≤ 1.5 mVA
– Nominal discharge current In (8/20) µs: 20 kA
– Maximum discharge current Imax (8/20) µs: 40 kA
– Follow current interrupt rating Ifi: 100 A
– Voltage protection level Up: ≤ 1.5 kV
– Residual voltage Ures: ≤ 0.4 kV (at In) ≤ 0.25 kV (at 10 kA), ≤ 0.15 kV (at 5 kA), ≤ 0.1 kV (at 3 kA)
– Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 1.5 kV
– TOV behavior at UT: 1200 V AC (200 ms / withstand mode)
– Response time tA: ≤ 100 ns
– Max. backup fuse with V-type through wiring: 80 A (gG)