FLT-SEC-T1+T2-1C-350/25-FM Surge protection Type 1+2 3Phase 25kA/Pole (10/350)
Type 1+2 special combined lightning current and surge arrester – FLT-SEC-T1+T2-1C-350/25-FM – 2905465
Plug-in lightning and surge arrester combination, in accordance with Type 1+2/Class I+II, for 1-phase power supply networks, with combined PE and N installed in one conductor (L1, PEN).
ออกใบกำกับภาษีได้
รับประกันสินค้า
฿5,280.00
รายละเอียดสินค้า
Type 1+2 special combined lightning current and surge arrester – FLT-SEC-T1+T2-1C-350/25-FM – 2905465
Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C … 80 °C
Ambient temperature (storage/transport) -40 °C … 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % … 95 %
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (5 – 500 Hz/2.5 h/X, Y, Z)
General
IEC test classification I + II
I
T1 + T2
T1
EN type T1 + T2
T1
IEC power supply system TN-C
TT
Mode of protection L-PEN
Mounting type DIN rail: 35 mm
Color light grey RAL 7035
traffic grey A RAL 7042
Housing material PA 6.6-FR 20 % GF
PBT-FR
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type DIN rail module, two-section, divisible
Number of positions 1
Surge protection fault message Optical, remote indicator contact
Protective circuit
Nominal voltage UN 240 V AC (TN-C)
240 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous voltage UC 350 V AC
Rated load current IL 125 A (< 55 °C)
Nominal discharge current In (8/20) µs 25 kA
Impulse discharge current (10/350) µs, charge 12.5 As
Impulse discharge current (10/350) µs, specific energy 160 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp 25 kA
Follow current interrupt rating Ifi 25 kA (264 V AC)
3 kA (350 V AC)
Short-circuit current rating ISCCR 25 kA (264 V AC)
3 kA (350 V AC)
Voltage protection level Up ≤ 1.5 kV
Residual voltage Ures ≤ 1.5 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 1.5 kV
TOV behavior at UT 415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
Response time tA ≤ 25 ns
Max. backup fuse with V-type through wiring 125 A (gG)
Max. backup fuse with branch wiring 315 A (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs 100 kA
Indicator/remote signaling
Switching function Changeover contact
Operating voltage 12 V AC … 250 V AC
125 V DC (200 mA DC)
Operating current 10 mA AC … 1 A AC
1 A DC (30 V DC)
Connection method Plug-in/screw connection via COMBICON
Screw thread M2
Tightening torque 0.25 Nm
Stripping length 7 mm
Conductor cross section flexible 0.14 mm² … 1.5 mm²
Conductor cross section solid 0.14 mm² … 1.5 mm²
Conductor cross section AWG 28 … 16
Connection data
Connection method Screw connection
Screw thread M5
Tightening torque 4.5 Nm
Stripping length 18 mm
Conductor cross section flexible 2.5 mm² … 35 mm²
Conductor cross section solid 2.5 mm² … 35 mm²
Conductor cross section AWG 13 … 2
Connection method Fork-type cable lug
Conductor cross section flexible 1.5 mm² … 16 mm²
สินค้าที่เด่น
เลขที่ 8 ซอยพัฒนาการ 97 ถนนพัฒนาการ
แขวงประเวศ เขตประเวศ กรุงเทพฯ 10250
Customer service
02-726-1585-88
โทรศัพท์
infos@bluestone.co.th
อีเมล
เลขที่ 8 ซอยพัฒนาการ 97 ถนนพัฒนาการ แขวงประเวศ เขตประเวศ กรุงเทพฯ 10250
บริษัท บลูสโตน จำกัด
บริษัท บลูสโตน จำกัด
เลขที่ 8 ซอยพัฒนาการ 97 ถนนพัฒนาการ แขวงประเวศ เขตประเวศ กรุงเทพฯ 10250
02-726-1585-88
โทรศัพท์
infos@bluestone.co.th
อีเมล
เลขที่ 8 ซอยพัฒนาการ 97 ถนนพัฒนาการ แขวงประเวศ เขตประเวศ กรุงเทพฯ 10250
บริษัท บลูสโตน จำกัด
© 2024 Bluestone All Rights Reserved
This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.
Strictly Necessary Cookie should be enabled at all times so that we can save your preferences for cookie settings.
If you disable this cookie, we will not be able to save your preferences. This means that every time you visit this website you will need to enable or disable cookies again.