2907920Replacement plug for type 3 surge protection from the PLT-SEC-…-UT/PT product series. Nominal voltage 24 V.
IEC power supply system: TN-S
Type: Male
Product type: Replacement plug
Product family: SEC Family
Number of positions: 2
Surge protection fault message: optical
Insulation characteristicsOvervoltage category: III
Pollution degree: 2
IEC test classification: III / T3
EN type: T3
Number of ports: One
Protective circuitMode of protection: L-N / L-PE / N-PE
Direction of action: 1L-N & N-PE
Nominal voltage UN: 24 V AC (TN-S)
Nominal frequency fN: 50 Hz (60 Hz)
Maximum continuous voltage UC: 34 V AC
Residual current IPE: ≤ 5 µA
Standby power consumption PC: ≤ 2.7 mVA (at UREF) / ≤ 4.8 mVA (at UC)
Reference test voltage UREF: 27 V AC
Nominal discharge current In (8/20) µs: 1 kA
Combination wave UOC: 2 kV
Voltage protection level Up (L-N) : ≤ 0.2 kV
Voltage protection level Up (L-PE) : ≤ 0.6 kV
Voltage protection level Up (N-PE) : ≤ 0.6 kV
TOV behavior at UT (L-N) : 50 V AC (120 min / safe failure mode)
TOV behavior at UT (L-PE) : 50 V AC (120 min / withstand mode)
Response time tA (L-N) : ≤ 25 ns
Response time tA (L-PE) : ≤ 100 ns
Response time tA (N-PE) : ≤ 100 ns
Short-circuit current rating ISCCR: 10 kA AC
Max. backup fuse with branch wiring: 32 A (gG / B / C)
Download datasheet