Type 2 surge protection plugF-MS 12 ST - 2817990Surge protection plug type 2, with N-PE total current spark gap for base element.
- IEC test classification: II, T2
- EN type: T2
- IEC power supply system: TN, TT
- Type: Male
- Product type: Replacement plug
- Number of positions: 1
- Surge protection fault message: optical
- Arrester can be tested with CHECKMASTER from software version: From SW rev. 1.10
Insulation characteristics- Overvoltage category: III
- Pollution degree: 2
- Mode of protection: N-PE
- Direction of action: N-PE
- Nominal voltage UN: 240/415 V AC (TN - only N-PE)240/415 V AC (TT - only N-PE)
- Nominal frequency fN: 50 Hz (60 Hz)
- Maximum continuous voltage UC: 260 V AC
- Residual current IPE: ≤ 5 µA
- Standby power consumption PC: ≤ 1.5 mVA
- Nominal discharge current In (8/20) µs : 20 kA
- Maximum discharge current Imax (8/20) µs: 40 kA
- Follow current interrupt rating Ifi: 100 A (260 V)
- Voltage protection level Up: ≤ 1.5 kV
- Residual voltage Ures: ≤ 0.4 kV (at In), ≤ 0.25 kV (at 10 kA), ≤ 0.15 kV (at 5 kA), ≤ 0.1 kV (at 3 kA)
- Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 1.5 kV
- TOV behavior at UT: 1200 V AC (200 ms / withstand mode)
- Response time tA: ≤ 100 ns
Download datasheet